Dimension Data – Savings

Dimension Data saves over 85% with the Electro Sense Proactive Energy Management System™

The Electro Sense Proactive Energy Management System™, which provides the most efficient, cost effective use of lighting possible,was installed in the Dimension Data  Buildings known as the Campus in Bryanston in late 2004 to; provide optimum control of the lighting system, generate maximum cost savings for Dimension Data and minimize electricity use.

Total Monthly Impact

The following table shows the total measured and verified impact of the DSM measures implemented in this project.

ElectricalEmissions ( kg )
MWhCO2NOXSOXParticlesWater
Baseline6009955300781923481421739223
Actual87333770282797061107420
Savings5136624530501644411360631803
Saving Percentage85.5%

Average Electricity Consumption in Different Periods of Time

This paragraph shows the baseline, the actual and the electricity savings for different TOU periods of time.

Weekdays Averages

morningmorningmorningmiddayeveningeveningevening
off-peakstandardpeakstandardpeakstandardoff-peak
Time00:00-06:0006:00-07:0007:00-10:0010:00-18:0018:00-20:0020:00-22:0022:00-00:00
BaselineKW157.23156.63161.13157.84151.06150.17149.7
MeasuredKW10.8981.54138.55143.6186.0740.1224.01
SavingsKW136.3475.0922.5814.2364.99110.05125.69
Percentage Savings86.7%47.9%14%9%43%73.2%84%

Saturday Averages

morningmorningmiddayeveningevening
off-peakstandardoff-peakstandardoff-peak
Time00:00-07:0007:00-12:0012:00-18:0018:00-20:0020:00-00:00
BaselineKW156.4154.55154.57155.37155.17
MeasuredKW11.6739.337.3218.4414.41
SavingsKW144.73115.25117.25136.93140.76
Percentage Savings92.5%74.6%75.9%88.1%90.7%

Sunday Averages

day
average
Time00:00-24:00
BaselineKW154.38
MeasuredKW20.61
SavingsKW134.22
Percentage Savings86.9%